Andros CM: Technical References
| - Supply input voltage |
15 V~ +/- 10% |
| - Idle input current (battery working) |
70 mA @ 10,4Vdc |
| - Working temperature range |
-20° + 60° C |
| - Display working temperature range |
-5° + 50° C |
| - Output voltage toANDROS PL |
12V~ +/- 10% 3VA |
| - Output voltage to PAROS |
12V (250mA Max) |
| - Relay output -NO contact |
Max 3A-resistive load @ 230Vac |
| - Open collector output - common 12Vdc |
Max 20mA - grounded |
| - Clock precision |
4ppm @ 25 °C |
| - Rechargeable Buffer battery |
NiMH 9,6V 700mAh |
| - Clock battery |
Lithium 3V 190mAh |
| - Autonomy at battery working |
Not greater than 5 hours |
| - Size |
160x90x75mm - 9 DIN rail mod. |
| - Weight |
650 gr |
| - Insulation class |
II (
double insulation
) |
Andros RDE:
Technical References
- Supply input voltage |
5 V+/- 10% |
- Idle input current |
50mA @ 5V |
- Working temperature range |
- 20° + 60° C |
- Size |
35,5 x 90 x 75 mm - 2 DIN rail mod. |
- Weight |
85 gr |
Andros TR:
Technical References
- Primary coil working voltage |
230 V~ +/- 10% 50/60Hz |
- Secondary coil nominal voltage |
15 V~ |
- Nominal output power |
20 VA |
- Working temperature range |
- 20° + 60° C |
- Size |
71 x 90 x 75 mm - 4 DIN rail mod. |
- Weight |
570 gr |
- Insulation class |
II (double insulation) |
- Secondary coil-Short circuit protection |
PTC restorable |
Andros PL:
Technical References
- Supply input voltage |
12 V~ +/- 10% |
- Idle input current |
20 mA @ 12V~ |
- Working temperature range |
- 20° + 60° C |
- Size |
35,5 x 90 x 75 mm - 2 DIN rail mod. |
- Weight |
100 gr |
- Insulation Class |
II (double insulation) |
12V Side-Power Line Carrier Communication - Technical References
-
2-poles 12V~ 50/60 Hz Communication line
-
2-ASK Modulation 112KHz Carrier
-
17 bits +17 bits strings
-
Poll wait (17 bit) and answer send (17 bit). No repetition
-
MANCHESTER bit coding (2msec, 4msec)
-
Transmission speed 166,6 Baud |
230V Side-Power Line Carrier Communication - Technical References
-
Communication over three-phase + neutral powerline 230V~ 50/60 Hz
-
2-ASK Modulation 112KHz Carrier
-
12 bit strings (control/command: bits 1÷4, address: bits 5÷12) |
Power Line Carrier Communication to Andros PL - Technical References
-
2-poles 12V~ 50/60 Hz Communication line
-
2-ASK Modulation 112KHz Carrier
-
17 bits +17 bits strings
-
Poll wait (17 bit) and answer send (17 bit). No repetition
-
MANCHESTER bit coding (2msec, 4msec)
-
Transmission speed 166,6 Baud
|
RS485 Communication References
- Communication line |
twisted and shielded 2 poles-line |
- Number of RS485 peripherals |
nr. 8 max |
- Link maximum length |
500 mt |
- RS485 interface insulation |
+/- 50V |
- Transmission speed |
9600Baud |
- Start bit |
1 |
- Data bit |
8 |
- Stop bit |
1 |
- Parity bit |
NO |
|